Topic |
Rule |
Plot Level |
Plot Area |
The minimum size of plot for High rise building or Building with a height of 15 meters and above shall be 1000.0 sq.mt.{As per Rule no. 35.1 Note 4}
|
Plot Width |
The minimum size of plot for High rise building or Building with a height of 15 meters and above shall be 1000.0 sq.mt.{As per Rule no. 35.1 Note 4}
|
Plot Depth |
The minimum size of plot for High rise building or Building with a height of 15 meters and above shall be 1000.0 sq.mt.{As per Rule no. 35.1 Note 4}
|
Access Width |
The minimum width of abutting road for any Building more than 13.3 mt. ht. shall be 6.1 mt.{As per Rule no. 35.1 Note 4}
|
Plot Frontage |
The minimum size of plot for High rise building or Building with a height of 15 meters and above shall be 1000.0 sq.mt.{As per Rule no. 35.1 Note 4}
|
FAR Area |
(1)
In Affordable Housing, the Floor Area Ratio-FAR shall be 3.5 {As per Rule No. 83.13}
(2)
For Adityapur Nagar Parishad, Max. 3.0 permissible FAR may be permitted for Commercial or Mercantile type Use {As per Annexure III}
|
Consumed FAR |
(1)
In Affordable Housing, the Floor Area Ratio-FAR shall be 3.5 {As per Rule No. 83.13}
(2)
For Adityapur Nagar Parishad, Max. 3.0 permissible FAR may be permitted for Commercial or Mercantile type Use {As per Annexure III}
|
Common Plot Area |
In case of multi-storied buildings/ Group Housing /Apartment building/ Industrial/ Assembly/ Educational/ Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover) {As per Rule No.33}
|
Common Plot |
(1)
; In case of multi-storied buildings/ Group Housing /Apartment building/ Industrial/ Assembly/ Educational/ Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover) {As per Rule No.33}
(2)
;
(3)
In case of multi-storied buildings/ Group Housing /Apartment building/ Industrial/ Assembly/ Educational/ Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover) {As per Rule No.33}
(4)
;
|
Tree Number |
Mini. 8 Trees shall be required for the Plot area above 1000.0 sq.mt. (As per Rule No. 20.1.6)
|
Margin Rule |
(1)
In case of buildings of more than 30m height, for every increase in height of 6.7 m. or fraction thereof or addition of two floor, 1m. in the front set back and 0.75 m. in the sides and rear setbacks shall be added {As per Rule No. 37 Table 14 and modified as per Notification from Govt. of Jharkhand 3141 dated 15/05/2017}
(2)
For Commercial & Storage buildings having plotarea above 1000 sq.mt., Margin required in Front shall be 9.0 mt., Rear 6.0 mt. and 6.0 mt. shall be provided on both side. {As per Rule No. 38.2.5}
|
PWork to PWork Margin |
Reqd Building to Building margin shall be 6 mt. or 1.5 times side setback required for the taller block whichever is high {As per Rule No. 38.1}
|
Basement Margin Rule |
In case of apartment/ group housing/commercial building and basements may be allowed to be constructed under the entire plot area leaving mini. 3 mt. space from the boundary of the premises {As per Rule No. 48}
|
Building Level |
Building Height |
For Group Housing, No height limitation shall be applicable except in areas near protected monuments and airport, etc {As per Chapter VI}
|
Floor Height |
(1)
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab){As per Rule No.42.2.1}
(2)
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab){As per Rule No.42.2.1}
(3)
o Every basement shall be in every part at least 2.4 m. in height from the floor to the soffit of the roof slab or ceiling and mini. Of 2.1 mr. below the soffit of beams {As per Rule No. 48}
|
Parapet Height |
Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level {As per Rule No. 42.5}
|
Below GL Floor Height |
,
|
Basement Floor No. |
Maximum two basements/cellars may be permitted to be constructed for the plot size above 750 sq.mt. leaving the prescribed set back/open space applicable to the building {As per Rule No. 48}
|
Floor Number |
For Affordable Housing, No floor number limitation shall be applicable {As per Chapter XI}
|
Lift Count |
(1)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(2)
For Residential Building height 12.0 mt. or above, above G+4 floors or if the number of flats is 16 or more, Mini. 1 Lift shall be required For every 16 flats or part thereof. {As per Rule No. 49.1.2}
(3)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(4)
For Non-Residential Building, Minimum number of lifts to be 2 for all non-residential building above ground + 2 and the minimum capacity shall be 6 persons per floor. {As per Rule No. 49.2.3 and as per Notification from Govt. of Jharkhand 3141 dated 15/05/2017}
|
Lift |
(1)
The area of lift well shall not be counted for F.A.R calculation)
(2)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(3)
The area of lift well at one floor only (not the sum of total area of lift well at every floor) shall be counted for F.A.R calculation)
(4)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(5)
-
(6)
The area of lift well shall not be counted for F.A.R calculation)
(7)
The area of lift well at one floor only (not the sum of total area of lift well at every floor) shall be counted for F.A.R calculation)
|
StairCase |
(1)
Width of Winding staircase shall be mini. 0.90 mt.,Maximum rise 0.20 mt. & Minimum tread 0.25 mt. & Cabin Height 2.1 mt. {As per Rule No. 83.18}
(2)
; No Rule Defined
(3)
Width of the Fire Stair case shall be mini. 0.90 mt.,Maximum rise 0.20 mt. & Minimum tread 0.25 mt. {As per Rule No. 43.5.3.6}
(4)
; Number of riser shall not exceed 16 per flight of stairs. {As per Rule No. 43.5.3.6}
(5)
No Rule Defined
(6)
; Number of riser shall not exceed 16 per flight of stairs. {As per Rule No. 43.5.3.6}
(7)
No Rule Defined
(8)
; No Rule Defined
|
Ramp |
No Need to Check Natural Slope width, Depth or height. ;
|
Ramp No. |
(1)
For parking spaces in basements and upper storey of parking floors, if car parking is more then 40 two ramp of minimum of 3.30m width if it is straight and 3.60m width if it is curved and 5.4m width if one ramp is required shall be provided
(2)
For parking spaces in basements and upper storey of parking floors, if car parking is less then 40 one ramp of minimum of 3.30m width if it is straight and 4.50m width if it is curved shall be provided
|
Arch Projection |
(1)
No need to check
(2)
Chhajja,Cornice or Weather shed of upto 0.75m width shall be permitted. {As per Rule No. 46.1}
|
Plot / Building Level |
Accessory Use |
(1)
-
(2)
No need to check distance from Building Refuse Chute
(3)
Common toilet of maximum size of 5 sq.mt shall be taken Free from FAR
(4)
No need to check distance from Building Toilet
(5)
-
(6)
No need to check distance from Building Sewage Treatment Plant
(7)
The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area
(8)
No need to check distance from Building RAIN WATER HARVESTING
(9)
No need to check distance from Building ENT.GATE
(10)
Guard room of max. 10 sq.mt. maximum size of 5 sq.mt shall be taken Free from FAR
(11)
No need to check distance from Building GUARD ROOM
(12)
-
(13)
No need to check distance from Building Under ground water tank
(14)
Entrance Lobby of maximum size of 12 sq.m. shall be taken Free from FAR
(15)
No need to check distance from Building Entrance Lobby
(16)
-
(17)
No need to check distance from Building SOLAR HEATING SYSTEM
(18)
Electric cabin or substation of maximum size of 4 sq.m. with minimum width or diameter of 2 m
(19)
No need to check distance from Building Generator Room
|
Accessory Use Number |
(1)
Provision of rainwater harvesting shall be mandatory for 300 sqm. and above size of plots-The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area Rain Water Harvesting
(2)
Provision of toilets for visitors and separate toilets for guards and drivers shall be provided for Multistoried for Commercial and multidwelling units including Apartments Toilet
(3)
In case of buildings with a height of 15.0 meters and above or ground coverage more than 500 sqm., the main entrance to the premise shall not be less than 5 (five) meters i n width in order to allow easy access to fire engine Entrance Gate
|
Building Level (Rooms) |