Topic |
Rule |
Plot Level |
Plot Area |
No rule provided for Min. Plot size for proposed Use or Multistoried Building {Updated as per JBBL, Amendment VIII dated 16/03/2021}
|
Plot Width |
No rule provided for Min. Plot size for proposed Use or Multistoried Building {Updated as per JBBL, Amendment VIII dated 16/03/2021}
|
Plot Depth |
No rule provided for Min. Plot size for proposed Use or Multistoried Building {Updated as per JBBL, Amendment VIII dated 16/03/2021}
|
Access Width |
The minimum width of abutting road for any Building more than 13.3 mt. ht. shall be 6.1 mt.{As per Rule no. 35.1 Note 4}
|
Plot Frontage |
No rule provided for Min. Plot size for proposed Use or Multistoried Building {Updated as per JBBL, Amendment VIII dated 16/03/2021}
|
FAR Area |
(1)
In Old Area, for Non-Residential Building on abutting roadwidth 12.20 (40 ft.) to 18.30 mt., the Floor Area Ratio-FAR shall be 2.5 {As per Rule No.39, Table 15}
(2)
For MANGO NAC, Max. 3.0 permissible FAR may be permitted for Commercial or Mercantile type Use {As per Annexure III}
|
Consumed FAR |
(1)
In Old Area, for Non-Residential Building on abutting roadwidth 12.20 (40 ft.) to 18.30 mt., the Floor Area Ratio-FAR shall be 2.5 {As per Rule No.39, Table 15}
(2)
For MANGO NAC, Max. 3.0 permissible FAR may be permitted for Commercial or Mercantile type Use {As per Annexure III}
|
Common Plot Area |
In every building area, at least 5% of the land shall be covered by plantation (tree cover). {As per Rule No.33}
|
Common Plot |
(1)
In every building area, at least 5% of the land shall be covered by plantation (tree cover). {As per Rule No.33}
(2)
;
|
Tree Number |
4-8 Trees shall be required for the Plot area above 250.0 and upto 1000.0 sq.mt. (As per Rule No. 20.1.6)
|
DriveWay Rule |
(1)
The minimum width of the drive way meant exclusively for 2 wheelers should be 3.0 mt {As per Rule No. 41.2}
(2)
For Plor area upto 2000 sq.mt., the minimum width or driveways should not be less than 3.60 mt. {As per Rule No. 41.2 and modified as per Notification from Govt. of Jharkhand 3141 dated 15/05/2017}
|
Margin Rule |
For Non-highrise Commercial Building upto 16.4 mt. Ht. having Plot Depth 21-27 mt. and Plot width 21-27 mt., Margin required in Front shall be 6.0 mt., Rear 4.0 mt. and 3.0 mt. shall be provided on both side. {As per Rule No. 36 Table 10 & 11}
|
Basement Margin Rule |
In case of apartment/ group housing/commercial building and basements may be allowed to be constructed under the entire plot area leaving mini. 2 mt. space from the boundary of the premises {As per Rule No. 48}
|
Building Level |
Building Height |
For old area, on Road width 12.20-18.30 mt., Permissible height shall in no case exceed(1.5 times the width oftheroadonwhichtheplot abuts) + Road widening + the front setback or 30.0 mt. {As per Rule No. 39.1 Table 15}
|
Floor Height |
(1)
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab){As per Rule No.42.2.1}
(2)
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab){As per Rule No.42.2.1}
(3)
o Every basement shall be in every part at least 2.4 m. in height from the floor to the soffit of the roof slab or ceiling and mini. Of 2.1 mr. below the soffit of beams {As per Rule No. 48}
|
Parapet Height |
(1)
Parapet of suitable height may be constructed to hide installation like water tank and for other such purpose {As per Rule No. 42.5 and Updated as per JBBL, Amendment VIII dated 16/03/2021}
(2)
Parapet of suitable height may be constructed to hide installation like water tank and for other such purpose {As per Rule No. 42.5 and Updated as per JBBL, Amendment VIII dated 16/03/2021}
(3)
Parapet of suitable height may be constructed to hide installation like water tank and for other such purpose {As per Rule No. 42.5 and Updated as per JBBL, Amendment VIII dated 16/03/2021}
|
Below GL Floor Height |
The minimum height of the ceiling of upper basement shall be 0.90m. and the maximum, 1.5 m. above the average surrounding ground level {As per Rule No. 48},
|
Basement Floor No. |
Individual residential and small commercial buildings, plot size upto minimum 750 Sq. Meter may have one basement {As per Rule No. 48}
|
Floor Number |
For old area location,on Road width 12.20-18.30 mt., Maximum Height 30 meter shall be allowed. {As per Rule No. 39.1 Table 15}
|
Lift Count |
(1)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(2)
For Non-Residential Building, Minimum number of lifts to be 2 for all non-residential building above ground + 2 and the minimum capacity shall be 6 persons per floor. {As per Rule No. 49.2.3 and as per Notification from Govt. of Jharkhand 3141 dated 15/05/2017}
|
Lift |
(1)
-
(2)
The area of lift well shall not be counted for F.A.R calculation)
(3)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(4)
The area of lift well at one floor only (not the sum of total area of lift well at every floor) shall be counted for F.A.R calculation)
(5)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
|
StairCase |
(1)
No Rule Defined
(2)
; No Rule Defined
(3)
No Rule Defined
(4)
; Number of riser shall not exceed 16 per flight of stairs. {As per Rule No. 43.5.3.6}
(5)
Width of Winding staircase shall be mini. 0.90 mt.,Maximum rise 0.20 mt. & Minimum tread 0.25 mt. & Cabin Height 2.1 mt. {As per Rule No. 83.18}
(6)
; No Rule Defined
(7)
Width of the Fire Stair case shall be mini. 0.90 mt.,Maximum rise 0.20 mt. & Minimum tread 0.25 mt. {As per Rule No. 43.5.3.6}
(8)
; Number of riser shall not exceed 16 per flight of stairs. {As per Rule No. 43.5.3.6}
|
Ramp |
No Need to Check Natural Slope width, Depth or height. ;
|
Ramp No. |
For parking spaces in basements and upper storey of parking floors, if car parking is less then 40 one ramp of minimum of 3.30m width if it is straight and 4.50m width if it is curved shall be provided
|
Plot / Building Level |
Accessory Use |
(1)
The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area
(2)
No need to check distance from Building RAIN WATER HARVESTING
(3)
No need to check distance from Building ENT.GATE
(4)
-
(5)
No need to check distance from Building SOLAR HEATING SYSTEM
|
Accessory Use Number |
(1)
Provision of Rain Water Harvesting shall be mandatory for any use {Updated as per JBBL, Amendment VIII dated 16/03/2021} Rain Water Harvesting
(2)
In case of buildings with a height of 15.0 meters and above or ground coverage more than 500 sqm., the main entrance to the premise shall not be less than 5 (five) meters i n width in order to allow easy access to fire engine Entrance Gate
|
Building Level (Rooms) |