Topic |
Rule |
Plot Level |
Plot Area |
The minimum size of plot for High school, Residential school category shall be 6000.0 sq.mt. {As per Rule No. 35.1, Table 7}
|
Plot Width |
The minimum size of plot for High school, Residential school category shall be 6000.0 sq.mt. {As per Rule No. 35.1, Table 7}
|
Plot Depth |
The minimum size of plot for High school, Residential school category shall be 6000.0 sq.mt. {As per Rule No. 35.1, Table 7}
|
Access Width |
The minimum width of abutting road for High school, Residential school category shall be 12.20 mt. {As per Rule No. 35.1, Table 7}
|
Plot Frontage |
The minimum size of plot for High school, Residential school category shall be 6000.0 sq.mt. {As per Rule No. 35.1, Table 7}
|
FAR Area |
(1)
For Educational, Institutional and Assembly building above 1000 sq.mt. Plot area, the Floor Area Ratio-FAR shall be 2.25 {As per Rule No. 39.3}
(2)
No Rule Define.
|
Consumed FAR |
(1)
For Educational, Institutional and Assembly building above 1000 sq.mt. Plot area, the Floor Area Ratio-FAR shall be 2.25 {As per Rule No. 39.3}
(2)
No Rule Define.
|
Common Plot Area |
In case of multi-storied buildings/ Group Housing /Apartment building/ Industrial/ Assembly/ Educational/ Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover) {As per Rule No.33}
|
Common Plot |
(1)
;
(2)
;
(3)
; ;
|
Tree Number |
Mini. 8 Trees shall be required for the Plot area above 1000.0 sq.mt. (As per Rule No. 20.1.6)
|
DriveWay Rule |
For Plor area above 2000 sq.mt., The minimum width or driveways should not be less than 4.50 mt. {As per Rule No. 41.2 and modified as per Notification from Govt. of Jharkhand 3141 dated 15/05/2017}
|
Margin Rule |
For Educational Building, Margin required in Front shall be 9.0 mt., Rear 6.0 mt. and 6.0 mt. shall be provided on both side. {As per Rule No. 38.2.1}
|
PWork to PWork Margin |
Reqd Building to Building margin shall be 6 mt. or 1.5 times side setback required for the taller block whichever is high {As per Rule No. 38.1}
|
Basement Margin Rule |
Basements/cellars may be permitted to be constructed leaving the prescribed set back/open space applicable to the building {As per Rule No. 48}
|
Building Level |
Building Height |
For old area, on Road width 12.20-18.30 mt., Permissible height shall in no case exceed(1.5 times the width oftheroadonwhichtheplot abuts) + Road widening + the front setback or 30.0 mt. {As per Rule No. 39.1 Table 15}
|
Floor Height |
(1)
For Educational Bulding, The height of all rooms shall not be less than 3.3 m measured from the surface of the floor to the lowest point of the ceiling
(2)
For Educational Bulding, The height of all rooms shall not be less than 3.3 m measured from the surface of the floor to the lowest point of the ceiling
(3)
o Every basement shall be in every part at least 2.4 m. in height from the floor to the soffit of the roof slab or ceiling and mini. Of 2.1 mr. below the soffit of beams {As per Rule No. 48}
|
Parapet Height |
(1)
Parapet of suitable height may be constructed to hide installation like water tank and for other such purpose {As per Rule No. 42.5 and Updated as per JBBL, Amendment VIII dated 16/03/2021}
(2)
Parapet of suitable height may be constructed to hide installation like water tank and for other such purpose {As per Rule No. 42.5 and Updated as per JBBL, Amendment VIII dated 16/03/2021}
(3)
Parapet of suitable height may be constructed to hide installation like water tank and for other such purpose {As per Rule No. 42.5 and Updated as per JBBL, Amendment VIII dated 16/03/2021}
|
Below GL Floor Height |
The minimum height of the ceiling of upper basement shall be 0.90m. and the maximum, 1.5 m. above the average surrounding ground level {As per Rule No. 48},
|
Basement Floor No. |
Maximum two basements/cellars may be permitted to be constructed for the plot size above 750 sq.mt. leaving the prescribed set back/open space applicable to the building {As per Rule No. 48}
|
Floor Number |
For old area location,on Road width 12.20-18.30 mt., Maximum Height 30 meter shall be allowed. {As per Rule No. 39.1 Table 15}
|
Passage |
No exit doorway shall be less than 1.00 m. in width. {As per Rule No.43.4.2} ;
|
Lift Count |
(1)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(2)
For Non-Residential Building, Minimum number of lifts to be 2 for all non-residential building above ground + 2 and the minimum capacity shall be 6 persons per floor. {As per Rule No. 49.2.3 and as per Notification from Govt. of Jharkhand 3141 dated 15/05/2017}
|
Lift |
(1)
The area of lift well shall not be counted for F.A.R calculation)
(2)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(3)
The area of lift well at one floor only (not the sum of total area of lift well at every floor) shall be counted for F.A.R calculation)
(4)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(5)
-
|
StairCase |
(1)
Width of Winding staircase shall be mini. 0.90 mt.,Maximum rise 0.20 mt. & Minimum tread 0.25 mt. & Cabin Height 2.1 mt. {As per Rule No. 83.18}
(2)
; No Rule Defined
(3)
No Rule Defined
(4)
; No Rule Defined
|
Ramp |
No Need to Check Natural Slope width, Depth or height. ;
|
Ramp No. |
For parking spaces in basements and upper storey of parking floors, if car parking is less then 40 one ramp of minimum of 3.30m width if it is straight and 4.50m width if it is curved shall be provided
|
Plot / Building Level |
Accessory Use |
(1)
Common toilet of maximum size of 5 sq.mt shall be taken Free from FAR
(2)
No need to check distance from Building Toilet
(3)
The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area
(4)
No need to check distance from Building RAIN WATER HARVESTING
(5)
No need to check distance from Building ENT.GATE
(6)
Entrance Lobby of maximum size of 12 sq.m. shall be taken Free from FAR
(7)
No need to check distance from Building Entrance Lobby
(8)
-
(9)
No need to check distance from Building SOLAR HEATING SYSTEM
|
Accessory Use Number |
(1)
Provision of Rain Water Harvesting shall be mandatory for any use {Updated as per JBBL, Amendment VIII dated 16/03/2021} Rain Water Harvesting
(2)
Provision of toilets for visitors and separate toilets for guards and drivers shall be provided for Multistoried for Commercial and multidwelling units including Apartments Toilet
(3)
In case of buildings with a height of 15.0 meters and above or ground coverage more than 500 sqm., the main entrance to the premise shall not be less than 5 (five) meters i n width in order to allow easy access to fire engine Entrance Gate
|
Building Level (Rooms) |
Auditorium16.41x12.57
|
No Rule Defined |
Auditorium16.41x23.58
|
No Rule Defined |
Class Room6.75x8.89
|
No Rule Defined |
Class Room6.75x9.81
|
No Rule Defined |
Class Room9.35x6.75
|
No Rule Defined |
Entrance10.12x7.13
|
No Rule Defined |
Entrance2.63x1.99
|
No Rule Defined |
Meetin7.79x5.52
|
No Rule Defined |
Reception7.79x3.67
|
No Rule Defined |
Room7.79x5.21
|
No Rule Defined |
Room7.79x5.52
|
No Rule Defined |
Room7.79x8.90
|
No Rule Defined |