Topic |
Rule |
Plot Level |
Plot Area |
The minimum size of plot for High rise building (building with a height of 16.40 meters and above) shall be 1000.0 sq.mt.{As per Rule No. 35.1, Table 7}
|
Plot Width |
The minimum size of plot for High rise building (building with a height of 16.40 meters and above) shall be 1000.0 sq.mt.{As per Rule No. 35.1, Table 7}
|
Plot Depth |
The minimum size of plot for High rise building (building with a height of 16.40 meters and above) shall be 1000.0 sq.mt.{As per Rule No. 35.1, Table 7}
|
Access Width |
The minimum width of abutting road for High rise building (building with a height of 16.40 meters and above) shall be 12.20 mt.{As per Rule No. 35.1, Table 7}
|
Plot Frontage |
The minimum size of plot for High rise building (building with a height of 16.40 meters and above) shall be 1000.0 sq.mt.{As per Rule No. 35.1, Table 7}
|
FAR Area |
(1)
In New Area, for Non-Residential Building on abutting roadwidth 24.40 mt. (80 ft.) and above, the Floor Area Ratio-FAR shall be 3.0 {As per Rule No.39, Table 15}
(2)
For this Authority, No Max. permissible FAR has been provided {As per Annexure III}
|
Consumed FAR |
(1)
In New Area, for Non-Residential Building on abutting roadwidth 24.40 mt. (80 ft.) and above, the Floor Area Ratio-FAR shall be 3.0 {As per Rule No.39, Table 15}
(2)
For this Authority, No Max. permissible FAR has been provided {As per Annexure III}
|
Common Plot Area |
In case of multi-storied buildings/ Group Housing /Apartment building/ Industrial/ Assembly/ Educational/ Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover) {As per Rule No.33}
|
Common Plot |
(1)
;
(2)
;
(3)
; ;
|
Tree Number |
Mini. 8 Trees shall be required for the Plot area above 1000.0 sq.mt. (As per Rule No. 20.1.6)
|
Margin Rule |
In case of buildings of more than 30m height, for every increase in height of 6.7 m. or fraction thereof or addition of two floor, 1m. in the front set back and 0.75 m. in the sides and rear setbacks shall be added {As per Rule No. 37 Table 14 and modified as per Notification from Govt. of Jharkhand 3141 dated 15/05/2017}
|
Basement Margin Rule |
In case of apartment/ group housing/commercial building and basements may be allowed to be constructed under the entire plot area leaving mini. 3 mt. space from the boundary of the premises {As per Rule No. 48}
|
Building Level |
Floor Height |
(1)
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab){As per Rule No.42.2.1}
(2)
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab){As per Rule No.42.2.1}
(3)
o Every basement shall be in every part at least 2.4 m. in height from the floor to the soffit of the roof slab or ceiling and mini. Of 2.1 mr. below the soffit of beams {As per Rule No. 48}
|
Parapet Height |
Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level {As per Rule No. 42.5}
|
Below GL Floor Height |
,
|
Basement Floor No. |
Maximum two basements/cellars may be permitted to be constructed for the plot size above 750 sq.mt. leaving the prescribed set back/open space applicable to the building {As per Rule No. 48}
|
Floor Number |
No Rule Defined
|
Passage |
No exit doorway shall be less than 1.00 m. in width. {As per Rule No.43.4.2} ;
|
StairCase |
(1)
Width of Winding staircase shall be mini. 0.90 mt.,Maximum rise 0.20 mt. & Minimum tread 0.25 mt. & Cabin Height 2.1 mt. {As per Rule No. 83.18}
(2)
; No Rule Defined
(3)
Width of the Fire Stair case shall be mini. 0.90 mt.,Maximum rise 0.20 mt. & Minimum tread 0.25 mt. {As per Rule No. 43.5.3.6}
(4)
; Number of riser shall not exceed 16 per flight of stairs. {As per Rule No. 43.5.3.6}
(5)
No Rule Defined
(6)
; Number of riser shall not exceed 16 per flight of stairs. {As per Rule No. 43.5.3.6}
(7)
No Rule Defined
(8)
; No Rule Defined
|
Ramp |
For parking spaces in basements and upper storey of parking floors, at least two ramps of minimum of 3.00m width if it is strait and 3.6 width if it is curved at any point, or one ramp of minimum 4.5 m width and with minimum slope gradient of 1:8 for depth up to 1.8m and 1:10 for more than 1.8m depth shall be provided. In the case of Hospitals, the slope of ramp shall not be greater than 1:20 {As per Rule No. 41.8} ;
|
Ramp No. |
(1)
-
(2)
For parking spaces in basements and upper storey of parking floors, if car parking is less then 40 one ramp of minimum of 3.30m width if it is straight and 4.50m width if it is curved shall be provided
|
Plot / Building Level |
Accessory Use |
(1)
Common toilet of maximum size of 5 sq.mt shall be taken Free from FAR
(2)
No need to check distance from Building Toilet
(3)
-
(4)
No need to check distance from Building Sewage Treatment Plant
(5)
The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area
(6)
No need to check distance from Building RAIN WATER HARVESTING
(7)
Electric cabin or substation of maximum size of 4 sq.m. with minimum width or diameter of 2 m
(8)
No need to check distance from Building AHU
(9)
-
(10)
No need to check distance from Building Waste water recycling
(11)
-
(12)
No need to check distance from Building Overhead WaterTank
(13)
No need to check distance from Building ENT.GATE
(14)
-
(15)
No need to check distance from Building Under ground water tank
(16)
-
(17)
No need to check distance from Building SOLAR HEATING SYSTEM
|
Accessory Use Number |
(1)
Provision of rainwater harvesting shall be mandatory for 300 sqm. and above size of plots-The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area Rain Water Harvesting
(2)
For Hospitals and Nursing Home type of Building, Provisions of Solar Water Heating System shall be done. Solar Water Heating System
(3)
Provision of toilets for visitors and separate toilets for guards and drivers shall be provided for Multistoried for Commercial and multidwelling units including Apartments Toilet
(4)
In case of buildings with a height of 15.0 meters and above or ground coverage more than 500 sqm., the main entrance to the premise shall not be less than 5 (five) meters i n width in order to allow easy access to fire engine Entrance Gate
|
Building Level (Rooms) |