Topic |
Rule |
Plot Level |
Plot Area |
The minimum size of plot for Primary/Upper Primary school category shall be 2000.0 sq.mt. {As per Rule No. 35.1, Table 7}
|
Plot Width |
The minimum size of plot for Primary/Upper Primary school category shall be 2000.0 sq.mt. {As per Rule No. 35.1, Table 7}
|
Plot Depth |
The minimum size of plot for Primary/Upper Primary school category shall be 2000.0 sq.mt. {As per Rule No. 35.1, Table 7}
|
Access Width |
The minimum width of abutting road for Primary/Upper Primary school category shall be 9.0 mt. {As per Rule No. 35.1, Table 7}
|
Plot Frontage |
The minimum size of plot for Primary/Upper Primary school category shall be 2000.0 sq.mt. {As per Rule No. 35.1, Table 7}
|
FAR Area |
(1)
For Educational, Institutional and Assembly building above 1000 sq.mt. Plot area, the Floor Area Ratio-FAR shall be 2.25 {As per Rule No. 39.3}
(2)
0.0
|
Consumed FAR |
(1)
For Educational, Institutional and Assembly building above 1000 sq.mt. Plot area, the Floor Area Ratio-FAR shall be 2.25 {As per Rule No. 39.3}
(2)
0.0
|
Common Plot Area |
In case of multi-storied buildings/ Group Housing /Apartment building/ Industrial/ Assembly/ Educational/ Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover) {As per Rule No.33}
|
Common Plot |
(1)
In case of multi-storied buildings/ Group Housing /Apartment building/ Industrial/ Assembly/ Educational/ Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover) {As per Rule No.33}
(2)
;
|
Tree Number |
Mini. 8 Trees shall be required for the Plot area above 1000.0 sq.mt. (As per Rule No. 20.1.6)
|
Margin Rule |
(1)
For Multistoried Building, having Building Height 16.40-19.25 mt.,Margin required in Front shall be 6.5 mt., Rear 4.5 mt. and 4.5 mt. shall be provided on both side. {As per Rule No. 37 Table 14}
(2)
For Educational Building, Margin required in Front shall be 9.0 mt., Rear 6.0 mt. and 6.0 mt. shall be provided on both side. {As per Rule No. 38.2.1}
|
PWork to PWork Margin |
Reqd Building to Building margin shall be 6 mt. or 1.5 times side setback required for the taller block whichever is high {As per Rule No. 38.1}
|
Building Level |
Building Height |
For old area, on Road width 12.20-18.30 mt., Permissible height shall in no case exceed(1.5 times the width oftheroadonwhichtheplot abuts) + Road widening + the front setback or 30.0 mt. {As per Rule No. 39.1 Table 15}
|
Floor Height |
(1)
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab){As per Rule No.42.2.1}
(2)
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab){As per Rule No.42.2.1}
(3)
The plinth or any part of a building shall be so located with respect to the surrounding ground level that adequate drainage of the site is assured. The height of the plinth (except in case of stilted parking) shall be not less than 0.45 mt. from the surrounding ground level {As per Rule No. 42.10}
(4)
For Educational Bulding, The height of all rooms shall not be less than 3.3 m measured from the surface of the floor to the lowest point of the ceiling
(5)
For Educational Bulding, The height of all rooms shall not be less than 3.3 m measured from the surface of the floor to the lowest point of the ceiling
|
Parapet Height |
Parapet walls and handrails provided on the edges of roof terraces, balcony, verandah, etc shall not be less than 1.0 m and not more than 1.2 m in height from the finished floor level {As per Rule No. 42.5}
|
Floor Number |
For old area location,on Road width 12.20-18.30 mt., Maximum Height 30 meter shall be allowed. {As per Rule No. 39.1 Table 15}
|
Passage |
No exit doorway shall be less than 1.00 m. in width. {As per Rule No.43.4.2} ;
|
Lift Count |
(1)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(2)
For Non-Residential Building, Minimum number of lifts to be 2 for all non-residential building above ground + 2 and the minimum capacity shall be 6 persons per floor. {As per Rule No. 49.2.3 and as per Notification from Govt. of Jharkhand 3141 dated 15/05/2017}
|
Lift |
(1)
The area of lift well shall not be counted for F.A.R calculation)
(2)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(3)
The area of lift well at one floor only (not the sum of total area of lift well at every floor) shall be counted for F.A.R calculation)
(4)
The lift shall have a minimum width 1.7 mt. and minimum depth 1.9 mt.{As per clause no 4 and page no. 14 NBC }
(5)
-
|
StairCase |
(1)
Width of Winding staircase shall be mini. 0.90 mt.,Maximum rise 0.20 mt. & Minimum tread 0.25 mt. & Cabin Height 2.1 mt. {As per Rule No. 83.18}
(2)
; No Rule Defined
(3)
No Rule Defined
(4)
; No Rule Defined
|
Plot / Building Level |
Accessory Use |
(1)
Common toilet of maximum size of 5 sq.mt shall be taken Free from FAR
(2)
No need to check distance from Building Toilet
(3)
The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area
(4)
No need to check distance from Building RAIN WATER HARVESTING
(5)
No need to check distance from Building ENT.GATE
(6)
-
(7)
No need to check distance from Building SOLAR HEATING SYSTEM
|
Accessory Use Number |
(1)
Provision of rainwater harvesting shall be mandatory for 300 sqm. and above size of plots-The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sq. m. of roof area Rain Water Harvesting
(2)
For Hostel type of Building, Provisions of Solar Water Heating System shall be done. Solar Water Heating System
(3)
Provision of toilets for visitors and separate toilets for guards and drivers shall be provided for Multistoried for Commercial and multidwelling units including Apartments Toilet
(4)
In case of buildings with a height of 15.0 meters and above or ground coverage more than 500 sqm., the main entrance to the premise shall not be less than 5 (five) meters i n width in order to allow easy access to fire engine Entrance Gate
|
Building Level (Rooms) |